Structure & Functions
Full metal-clad enclosed;
Air composite insulation;
Four compartments (circuit breaker, bus bar, cable and LV);
Independent pressure relief channel;
Reliable interlocking system;
Sufficient space for cable installation;
Intelligent panel-mounted heater indicator;
Lighting with optical fiber cold light source;
Intelligent switchgear system;
External dimension: Height: 1200mm 1600mm
Depth: 2600mm 2800mm
Width: 2400mm 2600mm
Main technical parameters
Standards: GB/IEC
Rated voltage: 40.5kV Rated frequency: 50Hz
Max. rated main bus bar current: 2500A Max. rated short-time withstand current: 31.5kA (4s)
Max. rated peak withstand current: 80kA Max. rated short-circuit breaking current: 31.5kA
Rated single capacitor bank breaking current: 630A Rated back-to-back capa